Upload Program to Memory Module Micrologix 1400

Hardware Comparison: MicroLogix 1400 Series Comparison and Selection Guide

The MicroLogix 1400 serial was designed to be small, versatile and expandable to adjust a diversity of command and communication needs.  Relying on the popular RSLogix 500 software, these controllers offering EtherNet/IP, as well as online editing of programming.  They also characteristic a larger number of I/O compared to other MicroLogix family members.  And the MicroLogix 1400 series tin enhance network functionality and offering a range of features to help build a customized control solution for a wide range of applications.

As function of a family of minor programmable logic controllers, the MicroLogix 1400 offers a pace up with an expansion of capabilities over other members in this family.  Built upon the successful capabilities of the MicroLogix 1100, the 1400 serial offers many of the same features but with a more robust feature set on some functionalities including:

  • Increased I/O – The 1400 increases the embedded digital I/O count from sixteen in the 1100 to 32.  It also doubles the embedded analog I/O on some versions from the 2 offered by the one thousand to as many as 4 on the 1400.  Its expansion I/O capabilities are greatly increased in the 1400 equally well, reaching a total of 256 I/O, upwards from 144.
  • High Speed Counters – The original MicroLogix 1000 had only 1 high speed counter operating at 40 kHz.  The 1400 serial, nevertheless, offers upwardly to six at 100kHz.
  • Motion Functionality – The 1400 series offers iii pulse width modulated motion controls at 40 kHz and 3 pulse railroad train outputs at 100kHz as well.  This is a footstep up compared to the 1100 series which just offers two 40 kHz motility controls at 40kHz each and two pulse railroad train outputs at 40 kHz every bit well.
  • Advice – Both the 100 and the 1400 offer a wide diverseness of communication inputs such every bit DeviceNet peer-to-peer networking and Ethernet /IP and both have web server capabilities.  Both too have Data Highway 485 (DH485) communication ports as well as RS-232 ports.  Nevertheless, the 1400 series comes with an additional 9-pin D-shell port for RS-232 communication.
  • Advice Networks – Both the 1000 and 1400 serial offer a broad selection of networks to work with.  Even so, in add-on to the standard network capabilities of the 1000, only the 1400 offers DNP3 over IP and Modbus TCP/IP.

The MicroLogix 1400 was built to handle a wide array of industrial control applications including industrial machinery, edifice automation, commercial machinery and even utility applications that required SCADA.  There are numerous advantages to using the MicroLogix 1400 over other controllers likewise every bit over controllers within the MicroLogix family.  These advantages include:

  • Communication Protocol Flexibility – The MicroLogix 1400 series allows users to switch from user set parameters to factory set up parameters.  This means the controller can be switched from Modbus RTU and ASCII protocols to a full-duplex mode to allow for upload and download capability.  It also allows the user to monitor or edit the program.  This is done by switching the controller toa full-duplex DF-1.
  • Memory and Program Flexibility – the 1400 has a larger retention which allows 10KB of user words along with 10 KB of user information.  The program can be tuned because the 1400 allows online editing so that changes can exist made while the controller is in use.
  • Information Logging and Recipe – Every bit information impacts the controller, advanced information logging capability allows up to 128 KB of retentiveness that can be used in analysis of the program.  It also allows for up to 64 KB of recipe storage.  This improves flexibility of operation past allowing batch changes for timers and counters.
  • Software Flexibility – Similar all MicroLogix controllers, the 1400 uses the RSLogix 500 platform and tin also use RSLogix Micro.

In that location are several different variants within the 1400 series.  Each of these variants are available under a specific catalog number and have slightly different capabilities and features.  These variants are:

  • 1766-L32BWA
  • 1766-L32AWA
  • 1766-L32BXB
  • 1766-L32BWAA
  • 1766-L32AWAA
  • 1766-L32BXBA

The number and letter structure gives some information as to capabilities.  But many features and functionality are bachelor across all variants such as:

  • Memory – Each has 10K of user plan and 10K of data space.
  • Data Logging and Recipe Storage – All variants have a full 128 Chiliad of data logging available and tin can support upwards to 64KB of recipe storage.  Note, the 64 KB of recipe storage is subtracted from the KB available for information logging and is not an additional amount.
  • Memory and Battery Backup – All variants accept both bombardment fill-in and a module for memory dorsum-upward.
  • Serial and EtherNet Ports – Each variant has a single RS232C/RS485 that are isolated.  They also have a RS232C that is non-isolated and uses a D-sub connector. All have a unmarried 10/100 EtherNet/IP port every bit well.
  • Serial and EtherNet Protocols – All 1400 variants support the full range of communication protocols and EtherNet protocols. These include both full and half-duplex DF1 likewise equally DF Radio Modern.  They also back up DH-485, and Modbus RTU as either a server or client and DNP as a client.

Other mutual features on all variants include floating point math, embedded real-time clocks, online editing and two trim potentiometers.

In addition to the flexibility offered by plug-in modules, additional features are available within variants to let users to choose a version that all-time suits their needs.  For comparing, here are the key differences between the available 1400 series variants:

  • Input Power – For input ability, the 1766-L32BWA, 1766-L32AWA, 1766-L32BWAA and 1766-L32AWAA operate off 120/240 5 AC, while the 1766-L32BXB and 1766-L32BXBA employ 24V DC.
  • Power Consumption – At that place is some deviation in power consumption for each variant depending on application.  The 1766-L32AWA and 1766-L32AWAA use 100 VA while the 1766-L32BWA and 1766-L32BWAA use 120 VA.  Coming in on the lower and are the 1766-L32BXB and the 1766-L32BXBA which utilize 7.5-53 Due west
  • Power Inrush – Just as at that place is a high/low terminate difference in power consumption, so to is power supply inrush lower depending on variant.  The 1766-L32AWA, 1766-L32AWAA, 1766-L32BWA and 1766-L32BWAA have inrushes at 120 V AC of 25 A for 8 ms and forty A for 4 ms at 240 5.  The 1766-L32BXB and the 1766-L32BXBA on the lower end have a 24 V DC inrush at 15 A for 20 ms.
  • Digital Inputs and Outputs – The 1766-L32BWA, 1766-L32WAA, use 12 fast 24V DC digital inputs and 8 normal 24V DC inputs.  These variants as well use 12 relays for digital outputs.  Coming in at 20 120 V DC digital inputs and 12 relay outputs are the 1766-L32AWA and the 1766-L32AWAA.  For the 1766-L32BXB and 1766-L32BXBA, each use 12 fast 24 V DC and 8 normal 24 5 DC digital inputs and each sport half-dozen relay, 3 fast DC and iii normal DC digital outputs.
  • Analog Outputs – There is a distinction between variants within the 1400 serial offer analog outputs with the 1766-L32BWA, 1766-L32AWA  and 1766-L32BXB having no analog outputs while the 1766-L32BWAA, 1766-L32AWAA and 1766-L32BXBA each offer four voltage inputs and two voltage outputs.
  • Loftier Speed Inputs – For loftier speed inputs, the 1766-L32BWA, 1766-L32BXB, 1766-L32BWAA and the 1766-L32BXBA all offer upwards to 6 channels at 100 kHz while the 1766-L32AWA and the 1766-L32AWAA take none.
  • PWM/PTO – For machines that crave movement controls for Pulse Width Modulated (PWM) signals and Pulse Train Output (PTO) signals, variants 1766-L32BXB and 1766-L32BXBA offer 2 aqueduct PTO at 100 kHz and PWM at forty kHz.

Relay and FET Output Loads – The maximum controlled load for the 1766-L32BXB and 1766-L32BXBA is 1080 VA.  For the 1766-L32BWA, 1766-L32AWA , 1766-L32BWAA and 1766-L32AWAA, the maximum controlled load is 1440 VA.

MicroLogix 1400 controllers have a serial number in addition to their catalog number.  This serial number indicates which generation of controller is existence used.  Series A indicates the initial introduction of the 1400 series line.  There are a few differences between series when using and programming a MicroLogix 1400 controller.

  • Communication Cable – The 1400 requires the employ of specific communication cables which may vary based on serial.  For example, cables 1763-NC01 and 1747-CP3 can be used on series A controllers and later.  Still, in that location is a long list of cables that tin can just be used on series C or later.  These include:
    • 1761-CBL-AM00
    • 1761-CBL-AP00
    • 1761-CBL-PM02
    • 1761-CBL-HM02
  • Software Release – The MicroLogix 1400 uses RSLogix 500 equally its software platform.  Series A controllers can use RSLogix 500 version 8.i or higher.  Series B and C must use RSLogix 500 version 8.3 or afterward.
  • Firmware – The determination of which firmware to employ volition largely depend on which functionality the user wants to enable.  Each successive firmware upgrade enables new functionality and then the user will demand to be enlightened of what is required of the control organisation.  For instance, Series A controllers can only flash firmware upgrades through FRN7.   For B and C series controllers, Allen-Bradley recommends using FRN-21.006, which introduced countersign enhancements to the programming along with other features.  Other firmware upgrades available by series is:
    • FRN 21.005 – Series B and Series C only
    • FRN 21.000 Series B and Serial C only
    • FRN 16.0 Series B only
    • FRN fifteen.5 Series B only
    • FRN 15.iii Series B merely
    • FRN 15 Series B only
    • FRN 12 Serial B only
    • FRN 11 Serial B just
    • FRN 10 Series B just
    • FRN 7 Serial A only
    • FRN 6 Series A only
    • FRN five Series A but
    • FRN 4 Series A only

The MicroLogix 1400 comes with an embedded spider web server.  This allows better command over data by enabling remote direction of both the controller and the command system.  This helps users conduct remote troubleshooting, program changes and other activities that save fourth dimension and travel.  Information technology is also flexible enough to allow both simple web pages too as customized views.  This also helps in situations where speed of information transfer to the web page is a concern due to isolated equipment that may still use radio modems.

The embedded web server improves user performance and flexibility and even has email capabilities.  However, use of the spider web server functionality is firmware sensitive.  For FRN 16 and college, current browsers can be supported.  However, earlier firmware may require lower level or older browsers such equally Internet Explorer 6.o of Firefox ii.0.0.xiv.

While not a base controller, the MicroLogix 1400 allows the use of a memory module during performance.  The memory module tin operate in ane of 2 means.  While the module does not increment available retention of the control unit of measurement itself, it tin can be used as a backup against loss of the program and information.  It can likewise improve agility and flexibility past allowing users to ship programs betwixt unlike controllers.

Posted on:

DO Supply Inc. makes no representations every bit to the abyss, validity, correctness, suitability, or accuracy of any information on this website and will not exist liable for whatsoever delays, omissions, or errors in this information or whatsoever losses, injuries, or damages arising from its display or apply. All the information on this website is provided on an "as-is" ground. Information technology is the reader's responsibleness to verify their own facts. Do Supply Inc. is non an authorized distributor and is not in anyway affiliated with Rockwell Automation. DO Supply Inc. makes no representation equally to your power or right to download, obtain, or employ any firmware provided past the product's manufacturer. To the extent you lot wish to use such firmware, information technology is your responsibility to comply with the terms of any applicable license or other such understanding related to the download, installation, or use of the firmware. Practice Supply makes no representation that the version of the firmware that is installed on whatsoever product it sells is appropriate for your needs or use. Further, Practise Supply Inc. does non sell, re-sell, or license software that may be needed to operate certain hardware and customers must obtain any necessary software licensing, maintenance, or upgrades from the manufacturer or other authorized source. To the extent whatsoever of the products sold by Do Supply requires software for operation, you acknowledge that DO Supply does not sell or license such software and that information technology is solely your responsibility to obtain the software or a proper license to utilize information technology from authorized sources.

goldbergexch1973.blogspot.com

Source: https://www.dosupply.com/tech/2020/09/25/micrologix-1400-series-comparison-and-selection-guide/

0 Response to "Upload Program to Memory Module Micrologix 1400"